Voltage
regulation of a transformer is defined as the change in
magnitude of the secondary (terminal) voltage, when full-load (rated load) of
specified power factor supplied at rated voltage is removed i.e reduced to
no-load with primary voltage (and frequency) kept constant, as a percentage of
the rated load terminal voltage.
Thus, voltage
regulation formula is given by
Where, V2fl =
rated secondary terminal voltage while supplying full-load at specified power
factor.
V20 = secondary voltage with secondary open (no-load)
Voltage
regulation (V.R) derivation
The transformer equivalent circuit, shown below, is used to
derive the expression for voltage regulation.
Its phasor diagram is shown below. Φ is the load impedance
angle.
From phasor diagram, by voltage regulation definition
Ó¨eq is the equivalent impedance angle of transformer.
AB can be projected horizontally as AD.
The voltage drops IReq
and IXeq are very small in a well designed transformer
, therefore, δ is negligible. Hence, OC≃OD.
Because ( IZeq/V
) = Zpu , therefore
approx V.R = Zpu
cos(Ó¨eq
- Φ)
As per our sign convention, Φ is positive for lagging power factor loads and
negative for leading power factor.
The above V.R formula shows that Voltage
regulation
depends on
(1) load power factor (or load impedance angle Φ )
(2) equivalent impedance of transformer Zeq
(3) equivalent impedance angle of transformer Ó¨eq
Improvement
of V.R
Regulation can be reduced by reducing Zeq . But Zeq
consists of Req and Xeq
. Therefore, Req and Xeq must be reduced.
Req is reduced
by taking windings of low resistance value.
Xeq is nothing but circuit representation of leakage
flux. Therefore, leakage flux must be
reduced to reduce Xeq . This is done by placing windings as close as
possible, by increasing transformer window height to width ratio etc.
Zero
Voltage Regulation
V.R = 0
Ó¨eq – Φ = 900
Φ = Ó¨eq –900 ...
for lagging power factor loads
Φ = 900 - Өeq ...
for leading power factor loads
So, load power factor (lagging/leading) must satisfy above conditions for zero voltage regulation.
Maximum
Regulation
V.R = maximum ,when cos(Өeq - Φ) = 1 or Өeq - Φ = 00
or Өeq = Φ
(lagging)
Thus, for maximum voltage
regulation of transformer , the
impedance angle Φ of a lagging load, must be equal to the
equivalent impedace angle Ó¨eq
of transformer.
Minimum
Regulation
Minimum
regulation is the maximum value of negative regulation.
V.R = Zpu cos(Өeq - Φ)
Therefore, minimum regulation = Zpu
cos[Ó¨eq
– (-900)]
= Zpu cos(Ó¨eq
+900)
= - Zpu sinÓ¨eq
= -Xpu
V.R
variation with load power factor
By putting various values of Φ in V.R = Zpu cos(Өeq
- Φ) ,the variation of voltage regulation
with power factor can be obtained as shown below.
Related concepts :-