Voltage Regulation of Transformer



Voltage regulation of a transformer is defined as the change in magnitude of the secondary (terminal) voltage, when full-load (rated load) of specified power factor supplied at rated voltage is removed i.e reduced to no-load with primary voltage (and frequency) kept constant, as a percentage of the rated load terminal voltage.

Thus, voltage regulation formula is given by
Transformer Voltage Regulation formula
Where,   V2fl = rated secondary terminal voltage while supplying full-load at specified power factor.
V20 = secondary voltage with secondary open (no-load)



Voltage regulation (V.R) derivation



The transformer equivalent circuit, shown below, is used to derive the expression for voltage regulation.

Voltage Regulation of Transformer


Its phasor diagram is shown below. Φ is the load impedance angle.

Transformer Voltage Regulation  phasor diagram


From phasor diagram, by voltage regulation definition

Transformer Voltage Regulation  phasor diagram


Ó¨eq is the equivalent impedance angle of transformer. AB can be projected horizontally as AD.

The voltage drops  IReq and  IXeq  are very small in a well designed transformer , therefore, δ is negligible. Hence, OCOD.


Because    ( IZeq/V ) = Zpu     , therefore
approx  V.R = Zpu cos(Ó¨eq - Φ)



As per our sign convention, Φ  is positive for lagging power factor loads and negative for leading power factor.

The above V.R formula shows that Voltage regulation depends on
(1) load power factor   (or load impedance angle Φ )
(2) equivalent impedance of transformer  Zeq
(3) equivalent impedance angle of transformer   Ó¨eq


Improvement of V.R

Regulation can be reduced by reducing Zeq . But Zeq consists of  Req and Xeq . Therefore, Req and Xeq  must be reduced.
Req  is reduced by taking windings of low resistance value.
Xeq is nothing but circuit representation of leakage flux. Therefore,  leakage flux must be reduced to reduce Xeq . This is done by placing windings as close as possible, by increasing transformer window height to width ratio etc.


Zero Voltage Regulation

V.R = 0
Ó¨eq – Φ = 900
Φ = Ó¨eq –900                ...  for lagging power factor loads
Φ = 900 - Ó¨eq               ...  for leading power factor loads



So, load power factor (lagging/leading) must satisfy above conditions for zero voltage regulation.


Maximum Regulation

V.R = maximum  ,when  cos(Ó¨eq - Φ) = 1    or    Ó¨eq - Φ = 00
or   Ó¨eq = Φ (lagging)

Thus, for maximum voltage regulation  of transformer , the impedance angle  Î¦  of a lagging load, must be equal to the equivalent impedace angle  Ó¨eq of transformer.


Minimum Regulation

Minimum regulation is the maximum value of negative regulation.
V.R = Zpu cos(Өeq - Φ)
Therefore,   minimum regulation = Zpu cos[Ó¨eq – (-900)]
= Zpu cos(Ó¨eq +900)
= - Zpu sinÓ¨eq

= -Xpu


V.R variation with load power factor



By putting various values of Φ in   V.R = Zpu cos(Ó¨eq - Φ)   ,the variation of voltage regulation with power factor can be obtained as shown below. 

variation of voltage regulation with power factor



Related concepts :-